Grounding requirements for metal cable trays

2025-05-10 Visits:1002

Metal cable trays and their supports, as well as metal cable conduits introduced or led out, must be reliably grounded (PE) or grounded (PEN) and comply with the following regulations:

1. The total length of metal cable trays and supports should be connected to the grounding (PE) or neutral (PEN) main line at no less than 2 points;

2. The two ends of the connecting plate between non galvanized cable trays shall be connected by a copper core grounding wire, and the minimum allowable cross-sectional area of the grounding wire shall not be less than 4mm2;

3. The two ends of the connecting plate between galvanized cable trays shall not be connected to the grounding wire, but there shall be no less than 2 connection fixing bolts with anti loosening nuts or anti loosening washers at both ends of the connecting plate.